banner

Products

Mutilzone Fire Evacuation Fire Alarm Conroller Fire System

Mutilzone Fire Evacuation Fire Alarm Conroller Fire System

Mutilzone Fire Evacuation Fire Alarm Conroller Introductions:1. AW-CFP2166-2 conventional fire alarm panel is designed b
SHARE

Description

Basic Info
Model NO. AW-CFP2166
Product Name Mutilzone Fire Evacuation Fire Alarm Conroller
Zones 1-32
Power Supply 110VAC/240VAC
Battery 12V2ah*2
Fire Relay Output Nc and No
Fault Relay Output Nc and No
Sounder Output 2 Circuits
Warranty 12months
Zone/Detector Maximumly Supports 20PCS
OEM & ODM Service Available
Transport Package EPE Inside, Carton Outside
Specification CE, iso
Trademark Asenware
Origin Guangdong, China
HS Code 853110000
Production Capacity 10000PCS/Year
Product Description
Mutilzone Fire Evacuation Fire Alarm Conroller
Introductions:1. AW-CFP2166-2 conventional fire alarm panel is designed based on EN54 part 2 & 4 standard.2. Adopted modularized design, flexible extendable capacity.3. Two-level control mode by a lock4.27VDC power supply output.5. FIRE PROTECTION, FIRE ROUTING and FAULT signal output, the output can be configured to dry relay type or wet sources type.6.2 channel general sounders output.7. Each zone has 1 circuit detectors input.8. Each zone can be disable by a button.9. It has RESET button to reset the panel.10. SILENCE button to stop BUZZER and SOUNDERS.11. EVACUATE button to start a manual fire alarm immediately.12. TEST button to test all LEDs orderly.13. Low-battery protection function, when battery voltage lower than 21VDC, battery will be cut off automatically until the mains power is on.14. Optional GSM module is available for fire alarm by SMS.Freeman ZhouGSM: 008613922805315Asenware, professional fire alarm solution provider.
ITEM1Zone panel2Zone panel4-8 Zone panel12-32 Zone panel
Model No.AW-CFP2166-01AW-CFP2166-02AW-CFP2166-04-8AW-CFP2166-12-32
Power specification
Mains supply voltage110VAC or 240VAC
Internal power supply27.2VDC
Total output current limited500mA @ 240VAC500mA @ 240VAC3A @ 240VAC3A @ 240VAC
Main supply monitor for faultYes
Battery protection for low voltageYes
Batteries (default configuration)12V2AH*2
Detector circuit specification
Number of circuit124-164-32
Line fault monitor for open circuitYes
Line fault monitor for short circuitYes
Line fault monitor for detector removalYes, if End of Line Monitor Unit fitted in place of End of Line Resistor
End of Line device6.8k Ω,5% tolerance, 0.25W (colour code-blue,grey,red,gold)
Detector continuity diodesSilicon 1N4001 or Schottky type (required if End of Line Monitor Unit fitted to give Detector Removal Fault)
Call point resistor value470 to 680 Ω, 0.225 or 0.5 watt
Maximum number of smoke/heat detectors per zone20 (based on a total detector current of 2mA, each detector consuming 100μA).Note: if End of Line Monitor Unit is fitted, for correct operation maxmum voltage drop must not exceed 12 volts.
Maximum number of manual call points per zoneNo limit
Sounder circuit specification
Number of general circuits2
End of line resistor value6.8k Ω,5% tolerance, 0.25W (colour code-blue,grey,red,gold)
Line fault monitor for open circuitYes
Line fault monitor for short circuitYes
Outputs fused AT400mA
Maximum number of bells @ 20mA of each sounder output20
Fuses
Battery fuse1.5A F 20mm
Sounder outputs500mA F 20mm
Fire and fault output
Output typeNC and NO relay
Maximum current100mA
Connection block
Largest acceptable conductor size2.5mm2
Smallest acceptable conductor size0.75mm2
Size and weight

Dimensions(mm)272*200*70mm320*231*90mm395X502X124362X565X124
Weight (without batteries)4kg5kg7kg8kg
Weight (with batteries)5.8kg6.8kg9.6kg12.5kg

Our Contact